Learn more
SolutionsProductsNewsSoftwareSupportContacts
Aranet products
Discover all the solutions and products we offer here
Aranet T/RH IP68 sensor

The wireless sensor measures temperature and relative humidity. The IP class 68 hermetic enclosure of the sensor ensures that no excessive moisture or dust particles can alter the readings, ensuring constant and reliable data monitoring. The sensor can be placed in harsh environmental conditions and withstand excessive humidity.

Get a quote
Share:
Overview
Specifications
Applications
  • Sensors are compatible only with Aranet base stations
  • Measures: temperature (-40°C to 60°C/ -40°F to 140 °F)
  • Measures: Relative humidity (0% to 100%)
  • Line-of-Sight range: up to 3 km/ 1.9mi
  • Operating environment: indoor and outdoor use
  • Transmitter power: 14 dBm
  • Data Transmission: 1, 2, 5, 10 minutes
  • Battery life: 10 years
  • Protection class: IP68
  • Dimensions: 35mmØx120mm/ 1.4inØx4.7in
IP class 68
10 year battery life
Temperature, relative humidity monitoring
At least 3km line-of-sight range
Overview
  • Sensors are compatible only with Aranet base stations
  • Measures: temperature (-40°C to 60°C/ -40°F to 140 °F)
  • Measures: Relative humidity (0% to 100%)
  • Line-of-Sight range: up to 3 km/ 1.9mi
  • Operating environment: indoor and outdoor use
  • Transmitter power: 14 dBm
  • Data Transmission: 1, 2, 5, 10 minutes
  • Battery life: 10 years
  • Protection class: IP68
  • Dimensions: 35mmØx120mm/ 1.4inØx4.7in
IP class 68
10 year battery life
Temperature, relative humidity monitoring
At least 3km line-of-sight range
Specifications

Aranet T/RH IP68 sensor Datasheet

Aranet T/RH IP 68 sensor
Measurements Temperature
Relative Humidity
Line of Sight Range 3km/1.9mi
Operating environment Indoor and Outdoor use
Transmitter power 14 dBm
Frequency Depends on base station instructions
Measurement range Temperature -40°C to 60°C/-40°F to 140°F
Relative Humidity 0% to 100%
Temperature measurement accuracy -10°C to 60°C/14°F to 140°F 0.4°C/0.72°F
-20°C to -10°C/-4°F to 14°F 0.6°C/1.08°F
-40°C to -20°C/-40°F to 14°F 0.9°C/1.62°F
Relative Humidity measurement accuracy 0 to 80% @ 30°C/86°F 4%
80% to 95% @ 30°C/86°F 6%
Response time Τ63%
4 minutes at 1 m/s airflow
Data Transmission 1, 2, 5, 10 minutes**
Data Protection Data encryption
Power options 1 AA Alkaline battery (Zn/Mn02)
1 AA Lithium battery (Li/FeS2)
Battery life @20°C/68°F Up to 7 years with Alkaline battery
Up to 10 years with Lithium battery
Operating temperature -20°C to 55°C/-4°F to 131°F with Alkaline battery
-40°C to 60°C/ -40°F to 140°F with Lithium battery
Operating humidity 0% to 100% non-condensing*
Dimensions 35mmØx120mm/ 1.4inØx4.7in
Weight 59g (2.1oz) with Alkaline battery
51g (1.8oz) with Lithium battery
Construction ASA Plastic
Membrane GORE
Protection class IP68
Marking CE, FCC
Compatible base stations
Aranet PRO, Aranet MINI
Included 1 AA Alkaline battery, string

 

* For best accuracy, recommended operating range is 20% to 80% RH (non-condensing) and 5°C to 60°C (41°F to 140°F).
Prolonged operation beyond these ranges may result in a shift of sensor reading, with slow recovery time.

 

** 1, 2, 5, 10 min interval supported from Aranet PRO v1.3.2 and 2, 5, 10 min from Aranet MINI v3.20.

 

Applications
Storage facilities
Agriculture
Food manufacturing
Museums/exhibition halls
Building management
Foodservice industries
Data centers
Pharma industry
/
What are you looking for

Our site uses cookies so that we can provide better service to our website users. Continuing to use aranet.com means you agree to our use of cookies.
If you’d like to find more, please visit aranet.com/terms-and-conditions

Get 10% off your first order!
Sign up for news and get 10% off your first order!
By submitting this registration form you agree to receive e-mail notifications from Aranet. You will be able to unsubscribe anytime.